B2D5 Maximum delivery temperature
Part B2 Heated water services · NCC 2019: B2.5, NSW B2.5(a)(iv)
The delivery temperature of heated water at the outlet of each sanitary fixture must be—
not more than 45 °C in any—
residential part of an aged care building; or
patient care area in a health-care building; or
part of an early childhood centre, or primary or secondary school, that is used by children; or
designated accessible facility in a common area of a Class 2 building, or in any part of a Class 3, Class 5, Class 6, Class 7, Class 8, Class 9a, Class 9b, Class 9c or Class 10 building; or
not more than 50 °C in all other cases.
Applications
B2D5 applies to all heated water installations intended for personal hygiene.
Changed in NCC 2025. See NCC 2025 Volume Three B2D5, or show what changed.
The delivery temperature of heated water at the outlet of … Class 2 building, or in any part of a Class 3, 3 or Class 5, Class 6, Class 7, Class 8, Class 9a, Class 9b, Class 9c or 5 to Class 10 building; or not more than 50 °C in … applies to all heated water installations intended for personal hygiene.