VIC B2D5 Maximum delivery temperature
Part B2 Heated water services · varies B2D5 Maximum delivery temperature
Delete clause B2D5 and insert VIC B2D5 as follows:
The delivery temperature of heated water at the outlet of each sanitary fixture must be—
not more than 45 °C in any—
residential part of an aged care building; or
patient care area in a health-care building; or
part of an early childhood centre, or primary or secondary school, that is used by children; or
designated accessible facility in a common area of a Class 2 building, or in any part of a Class 3, Class 5, Class 6, Class 7, Class 8, Class 9a, 9b, 9c or Class 10 building; or
not more than 50 °C in all other cases.
Applications
B2D5 applies to all heated water installations intended for personal hygiene.
Exemptions
B2D5(b) does not apply to the replacement of a water heater unit in the same location where the original installation did not require a temperature control valve.