Victoria variation · NCC 2022 Volume Three

VIC B2D5 Maximum delivery temperature

Part B2 Heated water services · varies B2D5 Maximum delivery temperature

Open on NCC Online ↗

Delete clause B2D5 and insert VIC B2D5 as follows:

The delivery temperature of heated water at the outlet of each sanitary fixture must be—

not more than 45 °C in any—

residential part of an aged care building; or

patient care area in a health-care building; or

part of an early childhood centre, or primary or secondary school, that is used by children; or

designated accessible facility in a common area of a Class 2 building, or in any part of a Class 3, Class 5, Class 6, Class 7, Class 8, Class 9a, 9b, 9c or Class 10 building; or

not more than 50 °C in all other cases.

Applications

B2D5 applies to all heated water installations intended for personal hygiene.

Exemptions

B2D5(b) does not apply to the replacement of a water heater unit in the same location where the original installation did not require a temperature control valve.

Not in NCC 2025. No VIC B2D5 in NCC 2025 Volume Three.