NSW B2D6 Temperature control devices
Part B2 Heated water services · varies B2D6 Temperature control devices
Delete clause B2D6 and insert NSW B2D6 as follows:
(1) A temperature control device used to deliver heated water in accordance with B2D5(a) must be a—
thermostatic mixing valve; or
thermostatically controlled tap.
(2) A temperature control device used to deliver heated water in accordance with B2D5(b) must be a—
thermostatic mixing valve; or
thermostatically controlled tap; or
tempering valve; or
temperature limited water heater with a maximum delivery temperature of 50°C marked in accordance with AS 3498.
(3) The required maximum delivery temperature must be achieved in accordance with AS/NZS 3500.4.
Applications
B2D6 only applies to—
all new heated water services; or
replacing a hot water heater, regardless of the type or location of the heater.
Exemptions
A temperature control device need not be installed if one or more, but not all, heating units in a manifold water heater are replaced.
Changed in NCC 2025. See NCC 2025 Volume Three NSW B2D6, or show what changed.
Delete clause B2D6 and insert NSW B2D6 as follows: (1) … in accordance with AS/NZS 3500.4. Applications B2D6 only applies to sanitary fixtures for personal hygiene purposes — all When installing new heated water services; services, including extensions or additions to an existing heated water service; or When replacing a hot water heater, regardless of the type or … need not be installed if one or more, but not all, heating units all water heaters in a manifold bank of water heater heaters are replaced.
Removed words are struck through; added words are highlighted. Comparison of the text only.