VIC B2D6 Temperature control devices
Part B2 Heated water services · varies B2D6 Temperature control devices
Delete clause B2D6 and insert VIC B2D6 as follows:
(1) A temperature control device used to deliver heated water in accordance with B2D5(a) must be a—
(a) thermostatic mixing valve; or
(b) thermostatically controlled tap.
(2) A temperature control device used to deliver heated water in accordance with B2D5(b) must be a—
thermostatic mixing valve; or
thermostatically controlled tap; or
tempering valve; or
temperature limited water heater.
(3) The required maximum delivery temperature must be achieved in accordance with AS/NZS 3500.4.
(4) Thermostatic mixing valve work must comply with AS 4032.3 Water Supply - Valves for the control of heated water supply temperatures - Part 3: Requirements for field testing, maintenance or replacement of thermostatic mixing valves, tempering valves and end of line temperature control devices.
Applications
B2D6 applies to all heated water installations intended for personal hygiene.