NSW 9.5.1 Smoke and heat alarm requirements
NSW Part 9.5 Smoke alarms and evacuation lighting · varies 9.5.1 Smoke alarm requirements
Delete clause 9.5.1 and insert NSW 9.5.1 as follows:
(1) Smoke alarms must—
be located in—
Class 1a buildings excluding any non-associated Class 10a private garages, subject to (2), in accordance with 9.5.2 and 9.5.4; and
Class 1b buildings in accordance with 9.5.3 and 9.5.4; and
comply with AS 3786, except that in a Class 10a private garage where the use of the area is likely to result in smoke alarms causing spurious signals, any other alarm deemed suitable in accordance with AS 1670.1 may be installed provided that smoke alarms complying AS 3786 are installed elsewhere in the Class 1 building; and
be powered from the consumer mains source where a consumer mains source is supplied to the building; and
be interconnected where there is more than one alarm.
(2) Heat alarms must—
be installed in a Class 10a private garage that is located beneath a garage top dwelling and not associated with that dwelling; and
be located on or near the ceiling; and
comply with AS 1603.3; and
be powered from the consumer mains source supplying the garage top dwelling where a consumer mains source is supplied to the building; and
be interconnected to the garage top dwelling smoke alarms required by 9.5.2.
(3) Where heat alarms required by (2) are installed, durable notices must be permanently fixed to the garage top dwelling and non-associated Class 10a private garage in prominent locations, indicating that—
a heat alarm is installed in the non-associated Class 10a private garage; and
the heat alarm is interconnected to the garage top dwelling smoke alarms.