NCC 2025 Volume Three
Part B6 Rainwater services
16 clauses · Open on NCC Online ↗
- B6O1 ObjectiveThe Objective of this Part is to— safeguard people from illness, injury or loss (including loss of amenity) due to the failure of a rainwater…
- B6F1 Rainwater serviceA rainwater service must be designed and installed so as to operate in a way that avoids the likelihood of inadvertent contamination of any drinking…
- B6P1 PressureThe points of discharge of a rainwater service must— have— a working pressure of not less than 50 kPa; and a static pressure within a building of…
- B6P2 VelocityWater velocity within the rainwater service pipework must not exceed 3 m/s for no less than 99% of the time that water is required during the peak…
- B6P3 Water efficiency NSWWhere rainwater is used for flushing of toilets or urinals, efficient use of rainwater must be achieved by— incorporation of— a cistern or flushing…
- B6P4 AccessAccess must be provided to components of a rainwater service that require maintenance or replacement, including mechanical devices and controls.
- B6P5 IsolationMeans of isolation must be provided to a rainwater service and components that require testing, maintenance, or replacement, including mechanical…
- B6P6 IdentificationPipes and pipe outlets that form part of a rainwater service must be clearly identified.
- B6P7 Uncontrolled dischargeThe likelihood of failure of, or uncontrolled discharge from, a rainwater service must be avoided.
- B6D1 Deemed-to-Satisfy Provisions VICWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements B6P1 to B6P7 are satisfied by complying with B6D2 to B6D7. (2) Where a…
- B6D2 General requirements SAA rainwater service must comply with Section 15 of AS/NZS 3500.1.
- B6D3 IdentificationRainwater pipework must be marked in accordance with AS/NZS 3500.1. (2) Rainwater outlet fittings must be marked in accordance with AS/NZS 3500.1.
- B6D4 Water efficiency NSWCisterns or flushing devices for water closet pans must— be a minimum of 3 Star WELS rating, discharging not more than 6 litres or 4.5 litres for a…
- B6D5 AccessAccess for maintenance of mechanical components and operational controls must be provided in accordance with AS/NZS 3500.1.
- B6D6 IsolationA means of isolation for the rainwater service, appliances and devices for testing and maintenance must be provided in accordance with AS/NZS 3500.1.
- B6D7 Bushfire prone areasA rainwater service in a designated bushfire prone area must be in accordance with AS 3959.