Victoria variation · NCC 2025 Volume Three

VIC B1D3 General requirements

VIC Part B1 Cold water services · varies B1D3 General requirements

Open on NCC Online ↗

Delete clause B1D3 and insert VIC B1D3 as follows:

(1) A cold water service must be in accordance with AS/NZS 3500.1.

(2) Notwithstanding (1), all pipes and fittings used above-ground that supply fire hydrant systems, including combined sprinkler and hydrant systems, must comply with the material requirements of AS 2419.1 for above-ground pipework as for hydrant system pipes and fittings.

(3) A hose tap must be provided adjacent to urinals in sanitary facilities that are open to the public.

Changed since NCC 2022. See NCC 2022 Volume Three VIC B1D3, or show what changed.

Delete clause B1D3 and insert VIC B1D3 as follows: (1) A cold water service must be in accordance with AS/NZS 3500.1. (2) Drinking water Notwithstanding (1), all pipes and fittings used above-ground that is not intentionally heated supply fire hydrant systems, including combined sprinkler and hydrant systems, must be delivered at a temperature comply with the material requirements of less than 40°C. AS 2419.1 for above-ground pipework as for hydrant system pipes and fittings. (3) A hose tap must be provided in men's public toilets adjacent to urinals in sanitary facilities that are open to the urinals. public.

Removed words are struck through; added words are highlighted. Comparison of the text only.