D3D7 Smoke lobbies
Part D3 Construction of exits · NCC 2019: D2.6
A smoke lobby required by D2D12 must—
have a floor area not less than 6 m2; and
be separated from the occupied areas in the storey by walls which are impervious to smoke, and—
have an FRL of not less than 60/60/– (which may be fire-protective grade plasterboard, gypsum block with set plaster, face brickwork, glass blocks or glazing); and
extend from slab to slab, or to the underside of a ceiling with a resistance to the incipient spread of fire of 60 minutes which covers the lobby; and
any construction joints between the top of the walls and the floor slab, roof or ceiling must be smoke sealed with intumescent putty or other suitable material; and
at any opening from the occupied areas, have smoke doors complying with S12C3 and S12C4 except that the smoke sensing device need only be located on the approach side of the opening; and
be pressurised as part of the exit if the exit is required to be pressurised under E2D4.
Clauses referred to
- D2D12 Travel via fire-isolated exits
- S12C3 General requirements for smoke doors
- S12C4 Construction Deemed-to-Satisfy for smoke doors
- E2D4 Fire-isolated exits