Deemed-to-Satisfy Provision · NCC 2025 Volume One

D2D13 External stairways or ramps in lieu of fire-isolated exits

Part D2 Provision for escape · NCC 2019: D1.8

Open D2D13 on NCC Online ↗

(1) An external stairway or ramp may serve as a required exit in lieu of a fire-isolated exit serving a storey below an effective height of 25 m, if the stairway or ramp is—

non-combustible throughout; and

protected in accordance with (3) if it is within 6 m of, and exposed to, any part of the external wall of the building it serves.

(2) For the purposes of this clause—

exposure under (1)(b), is measured in accordance with S5C2, as if the exit was a building element and the external wall of the building was a fire-source feature to the exit, except that the FRL required in S5C2(1)(a) must not be less than 60/60/60; and

the plane formed at the construction edge or perimeter of an unenclosed building or part such as an open-deck carpark, open spectator stand or the like, is deemed to be an external wall; and

openings in an external wall and openings under (3) and (4), are determined in accordance with C4D2.

(3) The protection referred to in (1)(b), must adequately protect occupants using the exit from exposure to a fire within the building, in accordance with one of the following methods:

The part of the external wall of the building to which the exit is exposed must have—

an FRL of not less than 60/60/60; and

no openings less than 3 m from the exit (except a doorway serving the exit protected by a –/60/30 fire door in accordance with C4D9(1)); and

any opening 3 m or more but less than 6 m from the exit, protected in accordance with C4D5 and if wall wetting sprinklers are used, they are located internally.

The exit must be protected by construction of a wall, roof, floor or other shielding element as appropriate in accordance with (4) from—

any part of the external wall of the building having an FRL of less than 60/60/60; and

any openings in the external wall.

(4) The wall, roof, floor or other shielding element required by (3)(b) must—

have an FRL of not less than 60/60/60; and

have no openings less than 3 m from the external wall of the building (except a doorway serving the exit protected by a –/60/30 fire door in accordance with C4D9(1)); and

have any opening 3 m or more but less than 6 m from any part of the external wall of the building protected in accordance with C4D5 and if wall wetting sprinklers are used, they are located on the side exposed to the external wall.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One D2D13.
Can't meet D2D13? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →

Clauses referred to

Defined terms used