D3D21 Wire barriers
Part D3 Construction of exits · NCC 2019: D2.16(d)
Where a required barrier is constructed of wire, it is deemed to meet the requirements of D3D19(1) if it is constructed in accordance with the following:
For horizontal wire systems—
when measured with a strain indicator, it must be in accordance with the tension values in Table D3D21a; or
must not exceed the maximum deflections in Table D3D21c.
For non-continuous vertical wire systems, when measured with a strain indicator, must be in accordance with the tension values in Table D3D21a (see Note 4).
For continuous vertical or continuous near vertical sloped wire systems—
must have wires of no more than 2.5 mm diameter with a lay of 7×7 or 7×19 construction; and
changes in direction at support rails must pass around a pulley block without causing permanent deformation to the wire; and
must have supporting rails, constructed with a spacing of not more than 900 mm, of a material that does not allow deflection that would decrease the tension of the wire under load; and
when the wire tension is measured with a strain indicator, it must be in accordance with the tension values in Table D3D21b and measured in the furthermost span from the tensioning device.
Table D3D21a Wire barrier construction – minimum required tension (N) for stainless steel horizontal wires
Wire dia. (mm)
Lay
Wire spacing (mm)
Clear distance between posts (mm)
600
800
900
1000
1200
1500
1800
2000
2500
2.5
7x7
60
55
190
263
415
478
823
1080
1139
X
80
382
630
730
824
1025
1288
X
X
X
100
869
1218
1368
X
X
X
X
X
X
2.5
1x19
60
35
218
310
402
585
810
1125
1325
X
80
420
630
735
840
1050
1400
1750
X
X
100
1140
1565
X
X
X
X
X
X
X
3.0
7x7
60
15
178
270
314
506
660
965
1168
1491
80
250
413
500
741
818
1083
1370
1565
X
100
865
1278
1390
1639
X
X
X
X
X
3.0
1x19
60
25
183
261
340
520
790
1025
1180
X
80
325
555
670
785
1015
1330
1725
1980
X
100
1090
1500
1705
1910
X
X
X
X
X
4.0
7x7
60
5
73
97
122
235
440
664
813
1178
80
196
422
480
524
760
1100
1358
1530
2130
100
835
1182
1360
1528
1837
2381
2811
3098
X
4.0
1x19
60
5
5
10
15
20
147
593
890
1280
80
30
192
300
415
593
1105
1303
1435
1844
100
853
1308
1487
1610
2048
2608
3094
3418
3849
4.0
7x19
60
155
290
358
425
599
860
1080
1285
1540
80
394
654
785
915
1143
1485
1860
2105
2615
100
1038
1412
1598
1785
2165
2735
X
X
X
Table Notes
Lay = number of strands by the number of individual wires in each strand. For example a lay of 7x19 consists of 7 strands with 19 individual wires in each strand.
Where a change of direction is made in a run of wire, the tensioning device is to be placed at the end of the longest span.
If a 3.2 mm wire is used the tension figures for 3.0 mm wire are applied.
This table may also be used for a set of non-continuous (single) vertical wires forming a barrier using the appropriate clear distance between posts as the vertical clear distance between the rails.
X = Not allowed because the required tension would exceed the safe load of the wire.
Tension measured with a strain indicator.
Table D3D21b Continuous wire barrier construction – minimum required tension (N) for vertical or near-vertical stainless steel wires where the maximum clear spacing between the rails is 900 mm
Wire dia. (mm)
Lay
Widest spacing between wires (mm)
Required tension (N)
2.5
7x19
80
145
100
310
110
610
2.5
7x7
80
130
100
280
110
500
Table Notes
Lay = number of strands by the number of individual wires in each strand. For example a lay of 7x19 consists of 7 strands with 19 individual wires in each strand.
Vertical wires require two pulley blocks to each 180° change of direction in the wire.
Near vertical wires may only require one pulley block for each change of direction.
Tension measured with a strain indicator.
The table only includes 7x7 and 7x19 wires due to other wires not having sufficient flexibility to make the necessary turns.
Table D3D21c Wire barrier construction – maximum permissible deflection of each wire in mm when a 2 kg mass is suspended at mid-span for stainless steel wires
Wire dia. (mm)
Wire spacing (mm)
Clear distance between posts (mm)
600
900
1200
1500
1800
2000
2.5
60
17
11
9
8
8
8
80
7
5
5
5
X
X
3.0
60
19
13
8
7
7
7
80
8
6
6
5
5
5
4.0
60
18
12
8
8
7
7
80
8
6
4
4
4
4
Table Notes
Where a change of direction is made in a run of wire the 2 kg mass must be placed at the middle of the longest span.
If a 3.2 mm wire is used the deflection figures for 3.0 mm wire are applied.
This table may also be used for a set of non-continuous (single) vertical wires forming a barrier using the appropriate clear distance between posts as the vertical clear distance between the rails. The deflection (offset) is measured by hooking a standard spring scale to the mid span of each wire and pulling it horizontally until a force of 19.6 N is applied.
X = Not allowed because the required tension would exceed the safe load of the wire.
This table has been limited to 60 mm and 80 mm spaces for 2.5 mm, 3 mm and 4 mm diameter wires because the required wire tensions at greater spacings would require the tension to be beyond the wire safe load limit, or the allowed deflection would be impractical to measure.
Tables
- Table D3D21a Wire barrier construction – minimum required tension (N) for stainless steel horizontal wires
- Table D3D21b Continuous wire barrier construction – minimum required tension (N) for vertical or near-vertical stainless steel wires where the maximum clear spacing between the rails is 900 mm
- Table D3D21c Wire barrier construction – maximum permissible deflection of each wire in mm when a 2 kg mass is suspended at mid-span for stainless steel wires