Deemed-to-Satisfy Provision · NCC 2025 Volume One
D3D6 Open access ramps and balconies
Part D3 Construction of exits · NCC 2019: D2.5
Where an open access ramp or balcony is provided to meet the smoke hazard management requirements of E2D4 to E2D13, it must—
have ventilation openings to the outside air which—
have a total unobstructed area not less than the floor area of the ramp or balcony; and
are evenly distributed along the open sides of the ramp or balcony; and
not be enclosed on its open sides above a height of 1 m except by an open grille or the like having a free air space of not less than 75% of its area.