F4D5 Accessible sanitary facilities
Part F4 Sanitary and other facilities · NCC 2019: F2.4
In a building required to be accessible —
accessible unisex sanitary compartments must be provided in accessible parts of the building in accordance with F4D6; and
accessible unisex showers must be provided in accordance with F4D7; and
at each bank of toilets where there is one or more toilets in addition to an accessible unisex sanitary compartment at that bank of toilets, not less than one sanitary compartment suitable for a person with an ambulant disability for use by males and not less than one sanitary compartment suitable for a person with an ambulant disability for use by females, each in accordance with AS 1428.1, must be provided; and
an accessible unisex sanitary compartment must contain a closet pan, washbasin, shelf or bench top and adequate means of disposal of sanitary products; and
the circulation spaces, fixtures and fittings of all accessible sanitary facilities provided in accordance with F4D6 and F4D7 must comply with the requirements of AS 1428.1; and
an accessible unisex sanitary facility must be located so that it can be entered without crossing an area reserved for one sex only; and
where two or more of each type of accessible unisex sanitary facility are provided, the number of left and right handed mirror image facilities must be provided as evenly as possible; and
where male sanitary facilities are provided at a separate location to female sanitary facilities, accessible unisex sanitary facilities are only required at one of those locations; and
an accessible unisex sanitary compartment or an accessible unisex shower need not be provided on a storey or level that is not required by D4D4(f) to be provided with a passenger lift or ramp complying with AS 1428.1.
Clauses referred to
- F4D6 Accessible unisex sanitary compartments
- F4D7 Accessible unisex showers
- D4D4 Parts of buildings to be accessible