Deemed-to-Satisfy Provision · NCC 2022 Volume One

F7D7 Sound insulation rating of internal services

Part F7 Sound transmission and insulation · NCC 2019: NT F5.6, F5.6

Open F7D7 on NCC Online ↗
Varied in NT. Check the variation for your state.

(1) If a duct or soil, waste or water supply pipe, including a duct or pipe that is located in a wall or floor cavity, serves or passes through more than one sole-occupancy unit, the duct or pipe must be separated from the rooms of any sole-occupancy unit by construction with an Rw + Ctr (airborne) not less than—

40 if the adjacent room is a habitable room (other than a kitchen); or

25 if the adjacent room is a kitchen or non-habitable room.

(2) If a stormwater pipe passes through a sole-occupancy unit, it must be separated in accordance with (1)(a) and (b).

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F7D7.
Can't meet F7D7? A Performance Solution must meet the Performance Requirements it satisfies: F7P1, F7P2, F7P3, F7P4. Start a Performance Solution →

State and territory variations all clauses side by side →