Deemed-to-Satisfy Provision · NCC 2025 Volume One

J4D5 Roof lights

Part J4 Building fabric · NCC 2019: J1.4

Open J4D5 on NCC Online ↗

Roof lights must have—

a total area of not more than 5% of the floor area of the room or space served; and

transparent and translucent elements, including any imperforate ceiling diffuser, with a combined performance of—

for Total system SHGC, in accordance with Table J4D5; and

for Total system U-Value, not more than U3.9.

Table J4D5 Roof lights – Total system SHGC

Roof light shaft index Note 1

Total area of roof lights up to 3.5% of the floor area of the room or space

Total area of roof lights more than 3.5% and up to 5% of the floor area of the room or space

<1.0

≤ 0.45

≤ 0.29

≥ 1.0 to < 2.5

≤ 0.51

≤ 0.33

≥ 2.5

≤ 0.76

≤ 0.49

Table Notes

The roof light shaft index is determined by measuring the distance from the centre of the shaft at the roof to the centre of the shaft at the ceiling level and dividing it by the average internal dimension of the shaft opening at the ceiling level (or the diameter for a circular shaft) in the same units of measurement.

The area of a roof light is the area of the roof opening that allows light to enter the building.

The total area of roof lights is the combined area for all roof lights serving the room or space.

Tables

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One J4D5.
Can't meet J4D5? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

Defined terms used