J7D4 Interior artificial lighting and power control
Part J7 Artificial lighting and power · NCC 2019: J6.3
(1) In a Class 4 part of a building, all artificial lighting of a room or space must be individually operated in accordance with Specification 40 by–
a manual switch; or
other control device; or
a combination of (a) and (b).
(2) Subject to (3) to (13), other than in a Class 4 part of a building, all artificial lighting must be controlled by demand-operated control devices in accordance with Specification 40.
(3) A room or space with regular occupancy may have a time switch installed that—
overrides demand-operated controls during the period of regular occupancy; and
complies with Specification 40.
(4) A room or space with less than 20 W of artificial lighting that is situated within a larger room or space, may be controlled by manual switch when the artificial lighting within the larger room or space is activated.
(5) A space within a carpark with regular occupancy for greater than 5000 hours per annum need not have demand-operated control.
(6) For the purposes of (3), (4) and (5) “regular occupancy” is when a room or space is–
occupied by more than 1 person per 40 m2; or
used more than once every 15 minutes.
(7) Demand-operated control must be provided in the sole-occupancy unit of a Class 3 building, other than where providing accommodation for people with a disability or the aged, to disable the artificial lighting, air-conditioning, local fans and bathroom heating when the sole-occupancy unit is unoccupied.
(8) A demand-operated control required by (2) must, for other than a single functional space such as an auditorium, theatre, swimming pool, sporting stadium or warehouse, not operate more than 250 m2 of lighting.
(9) In a Class 5, 6 or 8 building of more than 250 m2, artificial lighting in a natural lighting zone adjacent to windows must be separately controlled from artificial lighting not in a natural lighting zone in the same storey except where—
the room containing the natural lighting zone is less than 20 m2; or
the room’s natural lighting zone contains less than 4 luminaires; or
70% or more of the luminaires in the room are in the natural lighting zone.
(10) Artificial lighting in a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp must be controlled by a demand-operated control in accordance with Specification 40.
(11) Artificial lighting in a foyer, corridor and other circulation spaces—
of more than 250 W within a single zone; and
adjacent to windows,
must be controlled by a daylight sensor and dynamic lighting control device in accordance with Specification 40.
(12) Artificial lighting for daytime travel in the first 19 m of travel in a carpark entry zone must be controlled by a daylight sensor in accordance with Specification 40.
(13) The requirements of (1) to (12) do not apply to the following:
Emergency lighting in accordance with Part E4, including dedicated light sources for photoluminescent exit signs required by S25C3(a).
Where artificial lighting is needed for 24 hour occupancy such as for a manufacturing process, parts of a hospital, an airport control tower or within a detention centre.
Changed since NCC 2022. See NCC 2022 Volume One J7D4, or show what changed.
(1) All In a Class 4 part of a building, all artificial lighting of a room or space must be individually operated in accordance with Specification 40 by– a manual switch; or other control device; or a combination of (a) and (b). (2) An occupant activated device, such as Subject to (3) to (13), other than in a room security device, Class 4 part of a motion detector building, all artificial lighting must be controlled by demand-operated control devices in accordance with Specification 40, 40. (3) A room or space with regular occupancy may have a time switch installed that — overrides demand-operated controls during the like, period of regular occupancy; and complies with Specification 40. (4) A room or space with less than 20 W of artificial lighting that is situated within a larger room or space, may be controlled by manual switch when the artificial lighting within the larger room or space is activated. (5) A space within a carpark with regular occupancy for greater than 5000 hours per annum need not have demand-operated control. (6) For the purposes of (3), (4) and (5) “regular occupancy” is when a room or space is– occupied by more than 1 person per 40 m2; or used more than once every 15 minutes. (7) Demand-operated control must be provided in the sole-occupancy unit of a Class … accommodation for people with a disability or the aged, to cut power to disable the artificial lighting, air-conditioner, air-conditioning, local exhaust fans and bathroom heater heating when the sole-occupancy unit is unoccupied. (3) An artificial lighting switch or other (8) A demand-operated control device in (1) must — if an artificial lighting switch, be located in a visible and easily accessed position — in the room or space being switched; or in an adjacent room or space from where 90% of the lighting being switched is visible; and required by (2) must, for other than a single functional space such as an auditorium, theatre, swimming pool, sporting stadium or warehouse — if in a Class 5 building or a Class 8 laboratory, warehouse, not operate lighting for an area of more than 250 m2; or if in a Class 3, 6, 7, 8 (other than a laboratory) or 9 building, not operate lighting for an area of more than — 250 m2 for a space of not more than 2000 m2; or 1000 m2 for a space of more than 2000 m2. (4) 95% of the light fittings in a building or storey of a building, other than a Class 2 or 3 building or a Class 4 part of a building, of more than 250 m2 must be controlled by — a time switch in accordance with Specification 40; or an occupant sensing device such as — a security key card reader that registers a person entering and leaving the building; or a motion detector in accordance with Specification 40. (5) of lighting. (9) In a Class 5, 6 or 8 building of more … luminaires in the room are in the natural lighting zone. (6) (10) Artificial lighting in a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp, ramp must be controlled by a motion detector demand-operated control in accordance with Specification 40. (7) (11) Artificial lighting in a foyer, corridor and other circulation spaces … and dynamic lighting control device in accordance with Specification 40. (8) (12) Artificial lighting for daytime travel in the first 19 m … controlled by a daylight sensor in accordance with Specification 40. (9) (13) The requirements of (1), (2), (3), (4), (5), (6), (7) and (8) (1) to (12) do not apply to the following: Emergency lighting in accordance with Part E4. E4, including dedicated light sources for photoluminescent exit signs required by S25C3(a). Where artificial lighting is needed for 24 hour occupancy such … hospital, an airport control tower or within a detention centre. (10) The requirements of (4) do not apply to the following: Artificial lighting in a space where the sudden loss of artificial lighting would cause an unsafe situation such as — in a patient care area in a Class 9a building or in a Class 9c building; or a plant room or lift motor room; or a workshop where power tools are used. A heater where the heater also emits light, such as in bathrooms.
Removed words are struck through; added words are highlighted. Comparison of the text only.