Deemed-to-Satisfy Provision · NCC 2025 Volume One

J8D5 Spa pool heating and pumping

Part J8 Heated water supply and swimming pool and spa pool plant

Open J8D5 on NCC Online ↗
Varied in QLD. Check the variation for your state.

(1) Heating for a spa pool that shares a water recirculation system with a swimming pool must be by—

a solar heater; or

a heater using reclaimed heat from another process such as reject heat from a refrigeration plant; or

a geothermal heater; or

a gas heater that achieves a minimum gross thermal efficiency of 90%; or

a heat pump; or

a combination of (a) to (e).

(2) Where some or all of the heating required by (1) is by a gas heater or a heat pump, the spa pool must have—

a cover with a minimum R-Value of 0.05; and

a push button and a time switch to control the operation of the heater.

(3) A time switch must be provided to control the operation of a circulation pump for a spa pool having a capacity of 680 L or more.

(4) Where required, a time switch must be capable of switching electric power on and off at variable pre-programmed times and on variable pre-programmed days.

(5) Pipework carrying heated or chilled water for a spa pool must comply with the insulation requirements of J6D9.

(6) A building with gas heated water for spa pool heating must be provided with—

reserved electrical capacity sufficient to support future installation of air-source heat pump water heating equipment for the spa pool assuming a nominal coefficient of performance of 3.25; and

reserved space within the main electrical distribution board comprising at least one empty three-phase circuit breaker slot and 4 DIN rail spaces per 35 kW of water heating capacity, labelled to indicate reservation for future installation of water heating equipment for the spa pool; and

reserved space in the electrical riser or supply pathway for future the spa pool heating equipment sized in accordance with (a); and

reserved plant area with—

space to accommodate heating plant of 7 m² plus 0.04 m²/kW of heating capacity; and

sufficient ventilation openings to achieve airflow of 115 L/s per kW of heating capacity, with no recirculation of air; and

a hot water circulation system and associated coils and heat exchangers serving the spa pool, designed to operate a peak temperature of less than 50°C.

(7) The capacity and space required by (6) must be sufficient to serve the same design load used to specify any gas-powered spa pool water heating equipment.

New in NCC 2025. No J8D5 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet J8D5? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →