Deemed-to-Satisfy Provision · NCC 2025 Volume One

J8D4 Swimming pool heating and pumping

Part J8 Heated water supply and swimming pool and spa pool plant · NCC 2019: J7.4

Open J8D4 on NCC Online ↗
Varied in QLD. Check the variation for your state.

(1) Heating for a swimming pool must be by—

a solar heater; or

a heater using reclaimed heat from another process such as reject heat from a refrigeration plant; or

a geothermal heater; or

a gas heater that achieves a minimum gross thermal efficiency of 90%; or

a heat pump; or

a combination of (a) to (e).

(2) Where some or all of the heating required by (1) is by a gas heater or a heat pump, the swimming pool must have—

a cover with a minimum R-Value of 0.05; and

a time switch to control the operation of the heater.

(3) A time switch must be provided to control the operation of a circulation pump for a swimming pool.

(4) Where required, a time switch must be capable of switching electric power on and off at variable pre-programmed times and on variable pre-programmed days.

(5) Pipework carrying heated or chilled water for a swimming pool must comply with the insulation requirements of J6D9.

(6) A building with gas heated water for a swimming pool must be provided with—

reserved electrical capacity sufficient to support future installation of air-source heat pump water heating equipment for the swimming pool assuming a nominal coefficient of performance of 3.25; and

reserved space within the main electrical distribution board comprising at least one empty three-phase circuit breaker slot and 4 DIN rail spaces per 35 kW of water heating capacity, labelled to indicate reservation for future installation of water heating equipment for the swimming pool; and

reserved space in the electrical riser or supply pathway for future swimming pool heating equipment sized in accordance with (a); and

reserved plant area with—

space to accommodate heating plant of 7 m² plus 0.04 m²/kW of heating capacity; and

sufficient ventilation openings to achieve airflow of 115 L/s per kW of heating capacity with no recirculation of air; and

a hot water circulation system that operates at a peak temperature of less than 50°C.

(7) The capacity and space required by (6) must be sufficient to serve the same design load used to specify any gas-powered swimming pool water heating equipment.

(8) For the purpose of J8D4, a swimming pool does not include a spa pool.

Changed since NCC 2022. See NCC 2022 Volume One J8D4, or show what changed.

(1) Heating for a spa pool that shares a water recirculation system with a swimming pool must be by — a solar heater; … plant; or a geothermal heater; or a gas heater that — if rated to consume 500 MJ/hour or less, achieves a minimum gross thermal efficiency of 86%; or if rated to consume more than 500 MJ/hour, achieves a minimum gross thermal efficiency of 90%; or a … is by a gas heater or a heat pump, the spa swimming pool must have — a cover with a minimum R-Value of 0.05; and a push button and a time switch to control the operation of the … to control the operation of a circulation pump for a spa pool having a capacity of 680 L or more. swimming pool. (4) Where required, a time switch must be capable of … days. (5) Pipework carrying heated or chilled water for a spa swimming pool must comply with the insulation requirements of J6D9. (6) A building with gas heated water for a swimming pool must be provided with — reserved electrical capacity sufficient to support future installation of air-source heat pump water heating equipment for the swimming pool assuming a nominal coefficient of performance of 3.25; and reserved space within the main electrical distribution board comprising at least one empty three-phase circuit breaker slot and 4 DIN rail spaces per 35 kW of water heating capacity, labelled to indicate reservation for future installation of water heating equipment for the swimming pool; and reserved space in the electrical riser or supply pathway for future swimming pool heating equipment sized in accordance with (a); and reserved plant area with — space to accommodate heating plant of 7 m² plus 0.04 m²/kW of heating capacity; and sufficient ventilation openings to achieve airflow of 115 L/s per kW of heating capacity with no recirculation of air; and a hot water circulation system that operates at a peak temperature of less than 50°C. (7) The capacity and space required by (6) must be sufficient to serve the same design load used to specify any gas-powered swimming pool water heating equipment. (8) For the purpose of J8D4, a swimming pool does not include a spa pool.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J8D4? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →

Clauses referred to

Defined terms used