New South Wales variation · NCC 2025 Volume One

NSW C1V3 Fire spread via external walls

NSW Part C1 Fire resistance · varies C1V3 Fire spread via external walls

Open on NCC Online ↗

Delete clause C1V3 and insert NSW C1V3 as follows:

Compliance with C1P2 to avoid the spread of fire via the external wall of a building is verified when—

compliance with C1P2(1)(c) to avoid the spread of fire between buildings, where applicable, is verified in accordance with C1V1 or C1V2, as appropriate; and

the external wall system—

has been tested for external wall (EW) performance in accordance with AS 5113; and

has achieved the classification EW; and

if containing a cavity, incorporates cavity barriers and these cavity barriers have been included in the test performed under (i) at the perimeter of each floor; and

in a building of Type A construction, the building is protected throughout by a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and has—

sprinkler protection to balconies, patios and terraces, and where overhead sprinkler coverage is not achieved alongside the external wall, sidewall sprinkler heads are provided at the external wall for the extent of the balcony, patio or terrace where overhead sprinkler coverage is not achieved; and

for a building with an effective height more than 25 m—

monitored stop valves provided at each floor level arranged to allow the isolation of the floor level containing the stop valve while maintaining protection to the remainder of the building; and

the sprinkler system being capable of providing sufficient flow to serve the design area required by AS 2118.1 for the relevant hazard class on each floor level plus the design area required by AS 2118.1 for the floor level above, except where the former level is either the floor level below the uppermost roof, or any floor level that is wholly below ground; and

in a building of Type B construction, the building is—

a Class 5, 6, 7 or 8 building or Class 4 part of a building; or

a Class 2, 3 or 9 building that—

is protected throughout by a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; or

has any openings in external walls separated by a slab or other horizontal construction complying with C3D7(1)(d) as if the building were of Type A construction.

New in NCC 2025. No NSW C1V3 in NCC 2022 Volume One; it may have moved or been renumbered.

The national clause