S5C14 Type A fire-resisting construction — roof superimposed on concrete slab: Concession

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.4

Open S5C14 on NCC Online ↗

A roof superimposed on a concrete slab roof need not comply with S5C11 as to fire-resisting construction if—

the superimposed roof and any construction between it and the concrete slab roof are non-combustible throughout; and

the concrete slab roof complies with Table S5C11g.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S5C14.