S5C16 Type A fire-resisting construction — roof lights
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.6
If a roof is required to have an FRL or its covering is required to be non-combustible, roof lights or the like installed in that roof must—
have an aggregate area of not more than 20% of the roof surface; and
be not less than 3 m from—
any boundary of the allotment other than the boundary with a road or public place; and
any part of the building which projects above the roof unless that part has the FRL required of a fire wall and any openings in that part of the wall for 6 m vertically above the roof light or the like are protected in accordance with C4D5; and
any roof light or the like in an adjoining sole-occupancy unit if the walls bounding the unit are required to have an FRL; and
any roof light or the like in an adjoining fire-separated section of the building; and
if a ceiling with a resistance to the incipient spread of fire is required, be installed in a way that will maintain the level of protection provided by the ceiling to the roof space.