Specification clause · NCC 2025 Volume One
S5C17 Type A fire-resisting construction — internal columns and walls: Concession
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1:3.7
For a building with an effective height of not more than 25 m and having a roof without an FRL in accordance with S5C15, in the storey immediately below that roof, internal columns other than those referred to in S5C11(1)(d) and internal walls other than fire walls and shaft walls may have—
in a Class 2 or 3 building: FRL 60/60/60; or
in a Class 5, 6, 7, 8 or 9 building—
with rise in storeys exceeding 3: FRL 60/60/60; or
with rise in storeys not exceeding 3: no FRL.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S5C17.
Clauses referred to
- S5C15 Type A fire-resisting construction — roof: Concession
- S5C11 Type A fire-resisting construction — fire-resistance of building elements