Table J3D7u Metal-framed flat, skillion or cathedral roof – thermal bridging mitigation

Part J3 Elemental provisions for a Class 4 part of a building

Open Table J3D7u on NCC Online ↗
Minimum ceiling R-Value from Tables J3D7a to J3D7r, and J3D7(1)(f) as applicableOption 1– increase insulation between roof frame members to specified minimum R-ValueOption 2 – add a layer of continuous insulation with specified minimum R-Value above or below the roof frame members
1.01.50.13
1.52.50.30
2.03.50.30
2.55.00.40
3.06.00.60
3.5X0.60
4.0X0.60
4.5X0.60
5.0X0.60
5.5X0.60
6.0X0.60

Table Notes

Minimum R-Values are in-situ values. They account for compression of insulation.

X= not permitted.

Table for J3D7 Roofs and ceilings of a Class 4 part of a building

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J3D7u.