Table · NCC 2025 Volume One
Table S47C2c Part load evaluation points - outdoor wet bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Specification 47 Calculation of climate specific part load value for chillers
| Load | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 |
|---|---|---|---|---|---|---|---|---|
| 25% | 17 | 16 | 12 | 12 | 14 | 12 | 12 | 10 |
| 50% | 24 | 22 | 17 | 17 | 20 | 18 | 17 | 13 |
| 75% | 27 | 25 | 21 | 20 | 23 | 20 | 19 | 15 |
| 100% | 28 | 27 | 23 | 22 | 25 | 24 | 21 | 14 |
Table Notes
Load is the proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table for S47C2 Calculation of climate specific part load value for chillers
New in NCC 2025. No Table S47C2c in NCC 2022 Volume One; it may have moved or been renumbered.