Table · NCC 2025 Volume One

Table S47C2c Part load evaluation points - outdoor wet bulb temperature (°C), Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area

Specification 47 Calculation of climate specific part load value for chillers

Open Table S47C2c on NCC Online ↗
LoadCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8
25%1716121214121210
50%2422171720181713
75%2725212023201915
100%2827232225242114

Table Notes

Load is the proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table for S47C2 Calculation of climate specific part load value for chillers

New in NCC 2025. No Table S47C2c in NCC 2022 Volume One; it may have moved or been renumbered.