Table S47C2d Part load evaluation points - outdoor wet bulb temperature (°C), Class 3 or 9c building or Class 9a ward area
Specification 47 Calculation of climate specific part load value for chillers
| Load | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 |
|---|---|---|---|---|---|---|---|---|
| 25% | 19 | 18 | 12 | 14 | 17 | 14 | 14 | 10 |
| 50% | 24 | 22 | 17 | 18 | 21 | 19 | 17 | 13 |
| 75% | 27 | 25 | 20 | 20 | 23 | 21 | 19 | 14 |
| 100% | 29 | 27 | 24 | 23 | 26 | 23 | 20 | 17 |
Table Notes
Load is proportion of the total design load served by a connected group of chillers.
CZ = climate zone.
Table for S47C2 Calculation of climate specific part load value for chillers