Table · NCC 2025 Volume One

Table S47C2d Part load evaluation points - outdoor wet bulb temperature (°C), Class 3 or 9c building or Class 9a ward area

Specification 47 Calculation of climate specific part load value for chillers

Open Table S47C2d on NCC Online ↗
LoadCZ 1CZ 2CZ 3CZ 4CZ 5CZ 6CZ 7CZ 8
25%1918121417141410
50%2422171821191713
75%2725202023211914
100%2927242326232017

Table Notes

Load is proportion of the total design load served by a connected group of chillers.

CZ = climate zone.

Table for S47C2 Calculation of climate specific part load value for chillers

New in NCC 2025. No Table S47C2d in NCC 2022 Volume One; it may have moved or been renumbered.