Table · NCC 2025 Volume One
Table S5C21c Type B construction: FRL of external columns not incorporated in an external wall
Specification 5 Fire-resisting construction
| Distance from a fire-source feature | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Load bearing column — less than 18 m | 90/–/– | 120/–/– | 180/–/– | 240/–/– |
| Load bearing column — 18 m or more | –/–/– | –/–/– | –/–/– | –/–/– |
| Non-load bearing column | –/–/– | –/–/– | –/–/– | –/–/– |
Table for S5C21 Type B fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S5C21c.