Table S5C21b Type B construction: FRL of non-loadbearing parts of external walls

Specification 5 Fire-resisting construction

Open Table S5C21b on NCC Online ↗
Distance from a fire-source featureFRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Less than 1.5 m–/90/90–/120/120–/180/180–/240/240
1.5 m to less than 3 m–/60/30–/90/60–/120/90–/180/120
3 m or more–/–/––/–/––/–/––/–/–

Table for S5C21 Type B fire-resisting construction — fire-resistance of building elements

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S5C21b.