Table · NCC 2025 Volume One

Table S5C24a Type C construction: FRL of parts of external walls

Specification 5 Fire-resisting construction

Open Table S5C24a on NCC Online ↗
Distance from a fire-source featureFRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Less than 1.5 m90/90/9090/90/9090/90/9090/90/90
1.5 to less than 3 m–/–/–60/60/6060/60/6060/60/60
3 m or more–/–/––/–/––/–/––/–/–

Table for S5C24 Type C fire-resisting construction — fire-resistance of building elements

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S5C24a.