Table 13.3.3a Constant for solar heat gain coefficient (CSHGC): climate zones 1 to 7

Part 13.3 External glazing

Open Table 13.3.3a on NCC Online ↗
Floor typeVentilation opening areaClimate zone
12345 (lightweight wall)5 (concrete or brick wall)67
Floor in direct contact with the ground5%0.06720.05950.09450.06040.04840.06570.07860.0762
10%0.07180.06400.09850.06260.05380.06950.08170.0821
15%0.07700.06820.10010.06410.05690.07140.08320.0871
20%0.08270.07190.10070.06500.05870.07230.08400.0912
Suspended floor5%0.04310.03240.07680.06510.03340.06300.09630.0750
10%0.04970.04040.07830.06970.04260.06830.09890.0778
15%0.05410.04580.07920.07210.04770.07100.10010.0789
20%0.05700.04940.07960.07340.05050.07230.10070.0793

Table Notes

The ventilation opening area is the total area of each ventilation opening divided by the floor area of the storey, including any mezzanine.

No window may have a design ventilation opening greater than 90% because the window frame will always obstruct some of the area of the opening.

Where the ventilation opening area is more than 20%, the CSHGC value corresponding to 20% ventilation opening area is to be used.

Where the floor construction of a storey, including any mezzanine, is partly in direct contact with the ground and partly suspended, the constant is to be—

interpolated between the constants in proportion to the floor area of each floor type; or

the constant for a suspended floor.

If the ventilation opening area is between the values shown in this Table, the constant may be interpolated.