B1D5 Structural software
Part B1 Structural provisions · NCC 2019: B1.5
(1) Structural software used in computer aided design of a building or structure, that uses design criteria based on the Deemed-to-Satisfy Provisions of the BCA, including its referenced documents, for the design of steel or timber trussed roof and floor systems and framed building systems, must comply with the ABCB Protocol for Structural Software.
(2) Structural software referred to in (1) can only be used for buildings within the following geometric limits:
The distance from ground level to the underside of eaves must not exceed 6 m.
The distance from ground level to the highest point of the roof, neglecting chimneys, must not exceed 8.5 m.
The building width including roofed verandahs, excluding eaves, must not exceed 16 m.
The building length must not exceed five times the building width.
The roof pitch must not exceed 35 degrees.
(3) The requirements of (1) do not apply to design software for individual frame members such as electronic tables similar to those provided in—
AS 1684; or
NASH Standard Residential and Low-Rise Steel Framing Part 2.