Deemed-to-Satisfy Provision · NCC 2022 Volume One

D2D8 Width of exits and paths of travel to exits

Part D2 Provision for escape · NCC 2019: D1.6(b), (c), (d) and (e)

Open D2D8 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) The unobstructed width of each required exit or path of travel to an exit, except for ladders provided in accordance with D2D21, D3D23 or I3D5, and doorways, must be not less than—

1 m; or

1.8 m in a passageway, corridor or ramp normally used for the transportation of patients in beds within a treatment area or ward area; and

in a public corridor in a Class 9c aged care building, notwithstanding (2) and (3)—

1.5 m; and

1.8 m for the full width of the doorway, providing access into a sole-occupancy unit or communal bathroom.

(2) If the storey, mezzanine or open spectator stand accommodates more than 100 persons but not more than 200 persons, the aggregate unobstructed width of required exits or paths of travel to an exit, except for doorways, must be not less than—

1 m plus 250 mm for each 25 persons (or part) in excess of 100; or

1.8 m in a passageway, corridor or ramp normally used for the transportation of patients in beds within a treatment area or ward area.

(3) If the storey, mezzanine or open spectator stand accommodates more than 200 persons, the aggregate unobstructed width of required exits or paths of travel to an exit, except for doorways, must be not less than—

2 m plus 500 mm for every 60 persons (or part) in excess of 200 persons if egress involves a change in floor level by a stairway or ramp with a gradient steeper than 1 in 12; or

in any other case, 2 m plus 500 mm for every 75 persons (or part) in excess of 200.

(4) In an open spectator stand which accommodates more than 2000 persons, the aggregate unobstructed width of required exits or paths of travel to an exit, except for doorways, must be not less than 17 m plus a width (in metres) equal to the number in excess of 2000 divided by 600.

Changed in NCC 2025. See NCC 2025 Volume One D2D8, or show what changed.

(1) The unobstructed width of each required exit or path … access into a sole-occupancy unit or communal bathroom. (2) If the a fire compartment relying on one or more horizontal exits, a storey, a mezzanine or an open spectator stand accommodates more than 100 persons but not … beds within a treatment area or ward area. (3) If the a fire compartment relying on one or more horizontal exits, a storey, a mezzanine or an open spectator stand accommodates more than 200 persons, the aggregate … to the number in excess of 2000 divided by 600.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet D2D8? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P9. Start a Performance Solution →