Deemed-to-Satisfy Provision · NCC 2022 Volume One
D3D23 Fixed platforms, walkways, stairways and ladders
Part D3 Construction of exits · NCC 2019: SA D2.18(c), D2.18
Varied in SA. Check the variation for your state.
A fixed platform, walkway, stairway, ladder and any going and riser, landing, handrail or barrier attached thereto may comply with AS 1657 in lieu of D3D14, D3D15, D3D17, D3D18, D3D19, D3D20, D3D21 and D3D22 if it only serves—
machinery rooms, boiler houses, lift-machine rooms, plant-rooms, and the like; or
non-habitable rooms, such as attics, storerooms and the like that are not used on a frequent or daily basis in the internal parts of a sole-occupancy unit in a Class 2 building or Class 4 part of a building.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One D3D23.
Can't meet D3D23? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P9. Start a Performance Solution →
State and territory variations all clauses side by side →
Clauses referred to
- D3D14 Goings and risers
- D3D15 Landings
- D3D17 Barriers to prevent falls
- D3D18 Height of barriers
- D3D19 Openings in barriers
- D3D20 Barrier climbability
- D3D21 Wire barriers
- D3D22 Handrails