Table · NCC 2022 Volume One

Table J3D7t Metal-framed flat, skillion or cathedral roof — minimum Total R-Value to account for thermal bridging

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open Table J3D7t on NCC Online ↗
Ceiling insulation R-Value from Tables J3D7a to J3D7r, and J3D7(1)(f) as applicableMinimum Total R-Value to account for thermal bridging: heat flow downMinimum Total R-Value to account for thermal bridging: heat flow up
1.01.401.32
1.51.861.78
2.02.292.21
2.52.712.63
3.03.113.02
3.53.313.22
4.03.663.57
4.53.983.90
5.04.324.22
5.54.634.53
6.04.934.82

Table Notes

Minimum Total R-Values are in-situ values. They account for compression of insulation.

Direction of heat flow must be determined in accordance with Table J3D7v.

Table for J3D7 Roofs and ceilings of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D7t.