Deemed-to-Satisfy Provision · NCC 2025 Volume One

J8D3 Heated water supply

Part J8 Heated water supply and swimming pool and spa pool plant · NCC 2019: J7.3

Open J8D3 on NCC Online ↗
Varied in QLD. Check the variation for your state.

(1) Pipework circulating heated water for food preparation and sanitary purposes must be insulated in accordance with J6D9, including 500 mm along each branch line.

(2) Trace-heated pipework carrying heated water for food preparation and sanitary purposes must be insulated in accordance with J6D9.

(3) A building with gas heated water for food preparation and sanitary purposes must be provided with—

reserved electrical capacity sufficient to support future installation of air-source heat pump water heating equipment for food preparation and sanitary purposes assuming a nominal coefficient of performance of 3.25; and

reserved space within the main electrical distribution board comprising at least one empty three-phase circuit breaker slot and 4 DIN rail spaces per 35 kW of water heating capacity labelled to indicate reservation for future installation of heated water supply; and

reserved space in the electrical riser or supply pathway for future water heating equipment, sized in accordance (a); and

reserved plant area with—

space to accommodate heating plant of 7 m² plus 0.04 m²/kW of heating capacity; and

sufficient ventilation to achieve airflow of 115 L/s per kW of heating, with no recirculation of air.

(4) The capacity and space required by (3) must be sufficient to serve the same design load used to specify any gas-powered water heating equipment for food preparation and sanitary purposes.

Changed since NCC 2022. See NCC 2022 Volume One J8D3, or show what changed.

(1) Heating Pipework circulating heated water for a swimming pool food preparation and sanitary purposes must be by — a solar heater; or a heater using reclaimed heat from another process such as reject heat from a refrigeration plant; or a geothermal heater; or a gas heater that — if rated to consume insulated in accordance with J6D9, including 500 MJ/hour or less, achieves a minimum gross thermal efficiency of 86%; or if rated to consume more than 500 MJ/hour, achieves a minimum gross thermal efficiency of 90%; or a heat pump; or a combination of (a) to (e). mm along each branch line. (2) Where some or all of the heating required by (1) is by a gas heater or a heat pump, the swimming pool Trace-heated pipework carrying heated water for food preparation and sanitary purposes must have — a cover be insulated in accordance with a minimum R-Value of 0.05; and a time switch to control the operation of the heater. J6D9. (3) A time switch building with gas heated water for food preparation and sanitary purposes must be provided with — reserved electrical capacity sufficient to control support future installation of air-source heat pump water heating equipment for food preparation and sanitary purposes assuming a nominal coefficient of performance of 3.25; and reserved space within the operation main electrical distribution board comprising at least one empty three-phase circuit breaker slot and 4 DIN rail spaces per 35 kW of a circulation pump water heating capacity labelled to indicate reservation for a swimming pool. future installation of heated water supply; and reserved space in the electrical riser or supply pathway for future water heating equipment, sized in accordance (a); and reserved plant area with — space to accommodate heating plant of 7 m² plus 0.04 m²/kW of heating capacity; and sufficient ventilation to achieve airflow of 115 L/s per kW of heating, with no recirculation of air. (4) Where required, a time switch The capacity and space required by (3) must be capable of switching electric power on sufficient to serve the same design load used to specify any gas-powered water heating equipment for food preparation and off at variable pre-programmed times and on variable pre-programmed days. (5) Pipework carrying heated or chilled water for a swimming pool must comply with the insulation requirements of J6D9. (6) For the purpose of J8D3, a swimming pool does not include a spa pool. sanitary purposes.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J8D3? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →