Housing Provisions clause · ABCB Housing Provisions 2022

7.4.4 Installation of gutters

Part 7.4 Gutters and downpipes · NCC 2019: 3.5.3.4

Open 7.4.4 on NCC Online ↗

(1) Eaves gutters must be—

installed with a fall of not less than 1:500; and

supported by brackets securely fixed at stop ends, corners and at not more than 1.2 m centres; and

fitted with overflow measures capable of removing the overflow volume specified in Table 7.4.4a and Table 7.4.4b.

(2) Overflow measures in accordance with 7.4.6 and 7.4.7 are deemed to be capable of removing the overflow volume specified in those provisions.

(3) Where the overflow volume values for ridge-to-gutter lengths in Table 7.4.4a and roof catchment areas in Table 7.4.4b are not stated, interpolation may be used to determine the applicable overflow values.

(4) Valley gutters must—

be installed on a roof with a pitch more than 12.5 degrees; and

have dimensions in accordance with Table 7.4.4c for the relevant rainfall intensity; and

have minimum freeboard of not less than 15 mm; and

have a side angle of not less than 12.5 degrees.

(5) The requirement of (1)(c) does not apply to eaves gutters fixed to a verandah or an eave that is greater than 450 mm in width, which—

has no lining; or

is a raked verandah or a raked eave with a lining sloping away from the building.

Table 7.4.4a Overflow volume for continuous measure (L/s/m)

Design 5 minute duration rainfall intensity (mm/h) (from Table 7.4.3d)

Ridge to gutter length — 2 m

Ridge to gutter length — 4 m

Ridge to gutter length — 6 m

Ridge to gutter length — 8 m

Ridge to gutter length — 10 m

Ridge to gutter length — 12 m

Ridge to gutter length — 14 m

Ridge to gutter length — 16 m

150 mm/h

0.08 L/s/m

0.17 L/s/m

0.25 L/s/m

0.33 L/s/m

0.42 L/s/m

0.50 L/s/m

0.58 L/s/m

0.67 L/s/m

175 mm/h

0.10 L/s/m

0.19 L/s/m

0.29 L/s/m

0.39 L/s/m

0.49 L/s/m

0.58 L/s/m

0.68 L/s/m

0.78 L/s/m

200 mm/h

0.11 L/s/m

0.22 L/s/m

0.33 L/s/m

0.44 L/s/m

0.56 L/s/m

0.67 L/s/m

0.78 L/s/m

0.89 L/s/m

225 mm/h

0.13 L/s/m

0.25 L/s/m

0.38 L/s/m

0.50 L/s/m

0.63 L/s/m

0.75 L/s/m

0.88 L/s/m

1.0 L/s/m

250 mm/h

0.14 L/s/m

0.28 L/s/m

0.42 L/s/m

0.56 L/s/m

0.69 L/s/m

0.83 L/s/m

0.97 L/s/m

1.1 L/s/m

275 mm/h

0.15 L/s/m

0.31 L/s/m

0.46 L/s/m

0.61 L/s/m

0.76 L/s/m

0.92 L/s/m

1.1 L/s/m

1.2 L/s/m

300 mm/h

0.17 L/s/m

0.33 L/s/m

0.50 L/s/m

0.67 L/s/m

0.83 L/s/m

1.0 L/s/m

1.2 L/s/m

1.3 L/s/m

325 mm/h

0.18 L/s/m

0.36 L/s/m

0.54 L/s/m

0.72 L/s/m

0.90 L/s/m

1.1 L/s/m

1.3 L/s/m

1.4 L/s/m

350 mm/h

0.19 L/s/m

0.39 L/s/m

0.58 L/s/m

0.78 L/s/m

0.97 L/s/m

1.2 L/s/m

1.4 L/s/m

1.6 L/s/m

375 mm/h

0.21 L/s/m

0.42 L/s/m

0.63 L/s/m

0.83 L/s/m

1.0 L/s/m

1.3 L/s/m

1.5 L/s/m

1.7 L/s/m

400 mm/h

0.22 L/s/m

0.44 L/s/m

0.67 L/s/m

0.89 L/s/m

1.1 L/s/m

1.3 L/s/m

1.6 L/s/m

1.8 L/s/m

Table 7.4.4b Overflow volume for dedicated measure (L/s)

Design 5 minute duration rainfall intensity (mm/h) (from Table 7.4.3d)

Roof catchment area — 30 m2

Roof catchment area — 40 m2

Roof catchment area — 50 m2

Roof catchment area — 60 m2

Roof catchment area — 70 m2

150 mm/h

1.3 L/s

1.7 L/s

2.1 L/s

2.5 L/s

2.9 L/s

175 mm/h

1.5 L/s

1.9 L/s

2.4 L/s

2.9 L/s

3.4 L/s

200 mm/h

1.7 L/s

2.2 L/s

2.8 L/s

3.3 L/s

3.9 L/s

225 mm/h

1.9 L/s

2.5 L/s

3.1 L/s

3.8 L/s

4.4 L/s

250 mm/h

2.1 L/s

2.8 L/s

3.5 L/s

4.2 L/s

4.9 L/s

275 mm/h

2.3 L/s

3.1 L/s

3.8 L/s

4.6 L/s

5.3 L/s

300 mm/h

2.5 L/s

3.3 L/s

4.2 L/s

5.0 L/s

5.8 L/s

325 mm/h

2.7 L/s

3.6 L/s

4.5 L/s

5.4 L/s

6.3 L/s

350 mm/h

2.9 L/s

3.9 L/s

4.9 L/s

5.8 L/s

6.8 L/s

365 mm/h

3.1 L/s

4.2 L/s

5.2 L/s

6.3 L/s

7.3 L/s

400 mm/h

3.3 L/s

4.4 L/s

5.6 L/s

6.7 L/s

7.8 L/s

Table 7.4.4c Valley gutters — Dimensions

Design rainfall intensity mm/h

Sheet width (minimum, mm)

Effective depth (he), (minimum, mm)

Effective width (we), (minimum, mm)

≤200

355

32

215

>200 to ≤ 250

375

35

234

>250 to ≤300

395

38

254

>300 to ≤350

415

40

273

>350 to ≤400

435

43

292

Tables

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 7.4.4.