D3D24 Doorways and doors
Part D3 Construction of exits · NCC 2019: D2.19
(1) A doorway in a resident use area of a Class 9c building must not be fitted with—
a sliding fire door; or
a sliding smoke door; or
a revolving door; or
a roller shutter door; or
a tilt-up door.
(2) A doorway serving as a required exit or forming part of a required exit, or a doorway in a patient care area of a Class 9a health-care building—
must not be fitted with a revolving door; and
must not be fitted with a roller shutter or tilt-up door unless—
it serves a Class 6, 7 or 8 building or part with a floor area not more than 200 m2; and
the doorway is the only required exit from the building or part; and
it is held in the open position while the building or part is lawfully occupied; and
must not be fitted with a sliding door unless—
it leads directly to a road or open space; and
the door is able to be opened manually under a force of not more than 110 N; and
if fitted with a door which is power-operated—
it must be able to be opened manually under a force of not more than 110 N if there is a malfunction or failure of the power source; and
if it leads directly to a road or open space it must open automatically if there is a power failure to the door or on the activation of a fire or smoke alarm anywhere in the fire compartment served by the door.
(3) A power-operated door in a path of travel to a required exit, except for a door in a patient care area of a Class 9a health-care building as provided in (2), must be able to be opened manually under a force of not more than 110 N if there is a malfunction or failure of the power source.