New South Wales variation · NCC 2025 Volume One

NSW E2D2 Application of part

NSW Part E2 Smoke hazard management · varies E2D2 Application of part

Open on NCC Online ↗

Delete subclause E2D2(2) and insert NSW E2D2(2) as follows:

(2) In addition to the Deemed-to-Satisfy Provisions of E2D3 to E2D13, the following specific Deemed-to-Satisfy Provisions apply to the following Class 6 and Class 9b buildings:

For Class 6 buildings, in fire compartments more than 2000 m2—

not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit — must comply with E2D14; or

containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit — must comply with E2D15.

For Class 9b assembly buildings —

all assembly buildings — must comply with NSW E2D16; and

nightclubs, discotheques and the like — must comply with NSW E2D17; and

exhibition halls, museums and art galleries — must comply with NSW E2D18; and

other assembly buildings (not listed in (i) to (iii)) — must comply with NSW E2D19.

New in NCC 2025. No NSW E2D2 in NCC 2022 Volume One; it may have moved or been renumbered.

The national clause