Deemed-to-Satisfy Provision · NCC 2025 Volume One

J2D2 Application of Section J

Part J2 Energy efficiency · NCC 2019: J0.1

Open J2D2 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) For a Class 3 to 9 building, other than a Class 4 part of a building, Performance Requirement J1P1 is satisfied by complying with—

Part J4, for the building fabric; and

Part J5, for building sealing; and

Part J6, for air-conditioning and ventilation; and

Part J7, for artificial lighting and power; and

Part J8, for heated water supply and swimming pool and spa pool plant; and

J9D3, for facilities for energy monitoring; and

J9D5(2) to (4), for onsite renewable energy systems.

(2) For a Class 4 part of a building, Performance Requirement J1P2 is satisfied by complying with—

J3D3, using house energy rating software; or

the following—

J3D4, for ceiling fans; and

J3D5, J4D3(1) to (4), and Part J5, for general thermal construction; and

J3D7, for roofs; and

J3D8 and J3D11 to J3D13, or J3D9, for walls and glazing; and

J3D10, for floors.

(3) For a Class 4 part of a building, Performance Requirement J1P3 is satisfied by complying with—

for the net equivalent energy usage—

J3D14, for a Class 4 part of a building with a total floor area not greater than 500 m2; or

J3D15, using house energy rating software; and

Part J6, for air-conditioning and ventilation; and

Part J7, for artificial lighting and power.

(4) For a Class 3 to 9 building, Performance Requirement J1P4 is satisfied by complying with J9D4(1), J9D4(2) and J9D5(1).

Changed since NCC 2022. See NCC 2022 Volume One J2D2, or show what changed.

(1) For a Class 2 3 to 9 building, other than a sole-occupancy unit of a Class 2 building or a Class 4 part of a building, Performance Requirement J1P1 … and spa pool plant; and J9D3, for facilities for energy monitoring. monitoring; and J9D5(2) to (4), for onsite renewable energy systems. (2) For a sole-occupancy unit of a Class 2 building or a Class 4 part of a building, Performance Requirement J1P2 … or the following — J3D4, for ceiling fans; and J3D5, J3D6, J4D3, J4D7(3), J4D7(4) J4D3(1) to (4), and Part J5, for general thermal construction; and J3D7, for … walls and glazing; and J3D10, for floors. (3) For a sole-occupancy unit of a Class 2 building or a Class 4 part of a building, Performance Requirement J1P3 is satisfied by complying with — for the net equivalent energy usage — J3D14, for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building with a total … J7, for artificial lighting and power. (4) For a Class 2 3 to 9 building, Performance Requirement J1P4 is satisfied by complying with J9D4 J9D4(1), J9D4(2) and J9D5. J9D5(1).

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J2D2? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →